MGinternet use Ireland's leading Internet Data Centre, the Data Electronics Group in Dublin, Ireland, to ensure rock-solid reliability and security for our customers data and servers.

We maintain redundancy by locating our secondary, tertiary and back-up servers in different physical facilities.

Explore the headings here to learn about the infrastructure that supports our business.

 

Environment

  • Fully redundant individual close control air conditioning units based on a chiller and dry cooler system.
  • High performance, sensitive electronic equipment requires precise, reliable control of room temperature, humidity, and airflow.
  • Configured to monitor many variables and send alerts when entering the predetermined criteria ranges (e.g., high or low temperatures, high or low humidity, smoke detection, and mechanical problems).
  • 22 degrees Celsius (plus or minus 2 degrees C).
  • Relative humidity 50% (plus or minus 10%).
  • Air filtration to class EU5.

Back to Top

 

Security

  • Video surveillance cameras.
  • Security breach alarms.
  • 24-hour security personnel.
  • There are CCTV cameras mounted inside and outside of each ISC.
  • The video surveillance is monitored by the security control room 24x7.
  • The ISCs utilize a proximity card access system with mandatory pre-approved client lists and mandatory sign-in/sign-out procedures.
  • Customers are issued proximity-cards upon each visit, after presenting valid photo identification.
  • Customer names must be listed on a pre-approved client access list which is submitted prior to installation.

Back to Top

 

Power

  • AC Power of 220-240 Volts available up to 1000 Watts per cabinet.
  • A+B power.
  • Fully redundant UPS Systems, designed to provide 15 minutes of battery back-up time.
  • Fully redundant back-up generators with a 19 second start-up time and operating at full load after 30 seconds.
  • Fuel tanks capable of providing storage for a 72-hour full load diesel reserve.
  • Local 24 hour supplier contracts for extra fuel if needed.
  • Mains earth and a clean earth system with a resistance of less than 1 ohm (which meets standard NEN 1010).
  • Lightning protection system which meets standard NEN 1014.

Back to Top

 

Fire Protection

  • 60 minute rated firewalls
  • VESDA (Very Early Smoke Detection) type air-sampling system. This system actively and continuously samples air and operates independently of air movements. The samples are exposed to a high-intensity and broad-spectrum light source.
    Incident light scattered from smoke particles in the air sample passes through a series of optical components to a solid state light receiver.
  • Light is converted to an electronic signal and passed to the control system.
  • Ionization, Optical and Rate-of-Rise Smoke, and Heat Detectors.
  • INERGEN - inert gas fire suppression system will instantly extinguish any fire.